7030 & 7040 – Acoustic Wall-Mounted Louvres

7030 & 7040 – Acoustic Wall-Mounted Louvres

Features

  • Ventilation inlet and acoustic insulation
  • Ideal for limiting noise generation from compressor
    houses, pump houses, turbine rooms, generator
    rooms, etc.
  • Modular units, available in standard size or
    customised size
  • Factory or site assembled
  • Maintenance free

7030 and 7040 are acoustic half chevron louvres that can be assembled in modular units. The 7030 louvre unites aerodynamic and acoustic performance with an important free area. The 7040 is a high acoustic performance louvre, with moderate free area and important quantity of acoustic material.

7030-medium

7030: Medium to High Performance Louvre

  • Depth: 600 mm
  • Blades height: 150 mm
  • Blades pitch: 300 mm
  • Any combination of height and width is possible (mullion above 2000 mm wide)
  • Insulation: Rockwool 80 kg/m3
  • Material: Aluminium, ZincAlume or Galvanised
  • Colours: Standard Chromadek©, Standard COLORPLUS©, Standard RAL
  • Bird mesh as an optional extra
    (25 mm x 13 mm x 1.6 mm)
7040-high

7040: High Performance Louvre

  • Depth: 600 mm
  • Blades height: 235 mm
  • Blades pitch: 335 mm
  • Any combination of height and width is possible (mullion above 2000 mm wide)
  • Insulation: Rockwool 80 kg/m3
  • Material: Aluminium, ZincAlume or Galvanised
  • Colours: Standard Chromadek©, Standard COLORPLUS©, Standard RAL
  • Bird mesh as an optional extra
    (25 mm x 13 mm x 1.6 mm)

Standard Louvre Heights

Number of Intermediate Blades 7030 Standard Height (mm)
2 1400
3 1700
4 2000
5 2300
6 2600
7 2900

Standard Louvre Heights

Number of Intermediate Blades 7040 Standard Height (mm)
2 1189
3 1524
4 1859
5 2194
6 2529
7 2864

Standard heights show maximum free inlet area, however louvres can be manufactured to suit any opening dimension.

Acoustic Performances

Frequency (Hz) 7030 7040
Noise Reduction (dB) Noise Reduction (dB)
63 8 12.5
125 15.5 24
250 18 24
500 26 31.5
1000 35.5 36.5
2000 37 39.5
4000 33 34

Tests were carried out in accordance with ASTM E336-67T, section A2.3, “Test procedure for measuring transmission loss in non-laboratory type configuration”. The field transmission loss is determined as specified in section A2.3 E.336, and is defined as follows: FTL = NR-6.